Over-Under phase protector
Over-Under Phase protection.
WO-P2. 220V. For DIN rail and screw mounting.
Full instructions in English and Thai.
Over-Under Phase protection.
WO-P2. 220V. For DIN rail and screw mounting.
Full instructions in English and Thai.
Specification
Power consumption 2 VA
Input voltage 220 VAC 50/60 Hz.
Protection Varistor
Accuracy +/- 0.5% of normal voltage
Display 7-segment Red LED letter 0.39" (9.90 mm)
Adjustable Range Under voltage 2 to 20%
Over voltage 10 to 20%
Differential (Hysteresis) 1%
Time delay (Off) Under and Unbalance voltage: 1 to 5 seconds
Over voltage: 2 seconds (Fix)
Output type DPDT
Contact rating 5A at 250 VAC
Operations Mechanical: 2x107 times
Electrical: 1x105 times
Relay reset Automatic
Operating temperature 0o to 60o C
Mounting DIN Rail 35 mm or Screw mounting
Housing ABS UL 94 V-0
Wire fixing Screw terminal block (4 mm2 self lifting)
Indicator LED 3 mm
Dimension (mm) 54 x 71 x 105
Weight approx. 288 g